I wanted to refrain from leaving this feedback but having not received a penny of my money back as promised I feel I owe this to any of damiens future customers:
After Damien left the job uncompleted with no running water and a leaky sink and toilet, plus the old bathroom suite in the front garden, due to "personal issues", I had to pay out the same money again to another plumber to get the job finished.
Hers is his report of Damiens work:
DEAR SARAH, detailed below are the faults with your bathroom, the majority have now been rectified.
The 22mm hot and cold gate valves in the loft had been broken, by snapping the stem shut, basically overtightened, these were changed with new valves.
The tiling is attrocious , the worst ive ever seen, grout not wiped away.
The bath has not been correctly fixed to the wall, mearly silicone stuck, this will move with a fulll bath of water and a person in it.
There are no bath supports to take the weight if anyone sits on the bath edge it will probably crack the bath, these supports also act as a framework fot the bath panel, which is just flapping around and not fitted and has been badly cut around waste pipe.
The bath waste and handbasin waste runs up hill, how was the water going to drain away ? there were leaks on most joints aswell as the trap was leaking. It is honestly the worst set up ive ever seen, your origional plumber tried to bodge up his leaking joints by applying a brown hard settting putty around the joints, i have cut them out and will post to you as evidence.
The taps were loose.
The toilet is loose and not fixed and installed with no service valve. Poor.
The pop up waste for the handbasin is missing, probably because he doesnt no how to fit it.
The elecric shower was plumbed up to the tank cold water feed and not the Mains Water Supply, It would never had worked! Any plumber Knows electric showers are connected to the mains water supply.
The electric shower was wired up using no earth sleeve and using only a 2.5 mm cable. This is welll under-rated and would have melted and caused a fire. This instillation has now been condemmed.The shower was going to be just spurred into the ring main and not via a 45 amp pull chord and RCD .
Neary all his joints were push fits and he even managed to get leaks on those.
The shower screen has been installed 5 mm above the bath, and would have let the water run down on the outside of the bath to the floor.
All pipework is messy, what i call DIY job and not a proffesional installation.
This installation is the worst ive ever seen in 22 years of trading and i would doubt this plumbers compitence with ANY plumbing works, I would check to see if he is registered with any trade organisations and check if he holds any trade qualification or even insurance and would even report him to trading standards !
Its plumbers like this guy who gives us decent tradesman a bad name !